Đại lý phân phối Minimax tại Việt Nam
FMZ 5000 modules/cards
FMZ 5000 Loop AP XP redundant module
Part no.: 906186
Functional module for use in all design variants of the fire alarm system FMZ 5000. The loop module includestwo redundant processors for the operation in multi-zoneextinguishing systems in accordance with standards. Includes 2 detector loops for connection of up to 126 deviceseach. Instead of a loop, 2 branches can be connected to the module. Any number of T branches can be connected to each
loop. The loop devices can be fire detectors, input/outputmodules, control modules for sounders and loop couplers for the operation of conventional detectors in the loop. For use in potentially explosive atmospheres, IS-detectors can be connected to the loop via protocol interface and safety barriers.

Not included in delivery
- 4 Socket terminal strips FKCT 2.5/3-ST 901564
- Power distribution module 904093
Application in potentially explosive atmospheres
Only the following barriers are permitted:
- Safety barriere IS addressable 24 V 901324
- Loop AP protocol interface 901322
Technical specifications
| Operating voltage (module) | 18 V – 30 V DC |
| Quiescent current (module-bus) |
max. 85 mA DC |
| Supply current | max. 1440 mA DC |
| Loop current | max. 400 mA DC |
| Loop voltage | 27 V DC |
| Number of loops | 2 |
| Number of detectors per loop | 126 |
| Max. terminal cross-section | 2.5 mm2 (AWG 13) |
| Ambient temperature | -5 °C to +40 °C (+23 °F to +104 °F) |
| Relative humidity (IEC 721-3-3) |
max. 95 % no condensation |
| IP rating (EN 60529) | IP 20 |
| Enclosure | Polyamide PA6.6, green |
| Installation position | vertical |
| Mounting | Mounting rail 35 DIN 46277, top hat profile |
| Weight | 220 g (0.5 lbs) |
| Dimensions | 35 x 99 x 114.5 mm (WxHxD) 1.4 x 3.9 x 4.5 inch (WxHxD) |
| Total cable length | max. 2000 m (6562 ft) per loop |



Đánh giá