Control device
Release device EM Minimax
Thiết bị điều khiển cho hệ thống chữa cháy bằng khí trơ
Part: 885738 – 24 V DC
Part: 885739 – 230 V AC
The release device EM may be used only in accordance with the “documentation of special extinguishing systems” in fixed CO , argon, nitrogen, IG-55 and IG-541fire extinguishing systems. It is used for electrical release of lever valve.

Technical data
Temperature range
Solenoid ………. …………………-20 °C to +50 °C (-4 °F to 122 °F)
Magnetic force …………………………………………………………..44 N
Switching duration ……………………………………………………100 %
Voltage …………………………..24 V DC (18 – 28 V DC) / 230 V AC
Current ………………………………………………………1.04 A / 0.12 A
Stroke …………………………………………………………….9 mm (0.35″)
IP code ……………………………………………………………………..IP 54
(by accordingly covering of the pull and pressure rod side)


Đánh giá